Verified HVAC technical data

LG THERMA V R290 Monobloc Heat Pump

Current LG Business product pages and the official 2025 LG R290 catalogue define the THERMA V R290 Monobloc family with 7, 9, 12, 14 and 16 kW outdoor units in both single- and three-phase versions. The official technical table publishes one operating-point value set per capacity for the paired 1Ø/3Ø variants. UB40 7/9 kW units use the compact chassis; UB60 12-16 kW units use the larger chassis. No minimum active water volume or rated water flow is asserted here because those exact fields were not established from the reviewed source set.

Technical data reviewed: 2026-09-04 · 2025 LG R290 Catalogue [20250728]

Manufacturer sources: These values are maintained as technical intelligence. They do not state Moudouros stock, availability, price or commercial offer status.

Verified model data

ModelPhaseA7/W35COP W35A7/W55COP W55A−7/W35SCOP 35SCOP 55Max waterDimensionsSound powerRefrigerant
HM071HF UB40Single phase7 kW5.007 kW3.467 kW5.243.8675°C1320 × 1019 × 520 mm49 dBR290
HM091HF UB40Single phase9 kW4.709 kW3.159 kW5.203.8675°C1320 × 1019 × 520 mm50 dBR290
HM121HF UB60Single phase12 kW4.7012 kW3.3712 kW5.453.9775°C1560 × 1019 × 520 mm49 dBR290
HM141HF UB60Single phase14 kW4.5014 kW3.2714 kW5.383.9675°C1560 × 1019 × 520 mm51 dBR290
HM161HF UB60Single phase16 kW4.3016 kW3.1716 kW5.113.9275°C1560 × 1019 × 520 mm52 dBR290
HM073HF UB40Three phase7 kW5.007 kW3.467 kW5.243.8675°C1320 × 1019 × 520 mm49 dBR290
HM093HF UB40Three phase9 kW4.709 kW3.159 kW5.203.8675°C1320 × 1019 × 520 mm50 dBR290
HM123HF UB60Three phase12 kW4.7012 kW3.3712 kW5.453.9775°C1560 × 1019 × 520 mm49 dBR290
HM143HF UB60Three phase14 kW4.5014 kW3.2714 kW5.383.9675°C1560 × 1019 × 520 mm51 dBR290
HM163HF UB60Three phase16 kW4.3016 kW3.1716 kW5.113.9275°C1560 × 1019 × 520 mm52 dBR290
Final selection requires design heat loss, design outdoor condition, water temperature, emitter performance, hydraulics, DHW and electrical checks.