Verified HVAC technical data

LG THERMA V R290 Monobloc Heat Pump

Compare manufacturer-sourced model data for THERMA V R290 Monobloc. Match operating conditions and electrical supply before requesting a project-specific review. Technical reference coverage does not confirm product availability.

Technical data reviewed: 2026-09-04 · 2025 LG R290 Catalogue [20250728]

Manufacturer sources: These values are maintained as technical intelligence. They do not state Moudouros stock, availability, price or commercial offer status.

Verified model data

ModelPhaseA7/W35COP W35A7/W55COP W55A−7/W35SCOP 35SCOP 55Max waterDimensionsSound powerRefrigerant
HM071HF UB40Single phase7 kW5.007 kW3.467 kW5.243.8675°C1320 × 1019 × 520 mm49 dBR290
HM091HF UB40Single phase9 kW4.709 kW3.159 kW5.203.8675°C1320 × 1019 × 520 mm50 dBR290
HM121HF UB60Single phase12 kW4.7012 kW3.3712 kW5.453.9775°C1560 × 1019 × 520 mm49 dBR290
HM141HF UB60Single phase14 kW4.5014 kW3.2714 kW5.383.9675°C1560 × 1019 × 520 mm51 dBR290
HM161HF UB60Single phase16 kW4.3016 kW3.1716 kW5.113.9275°C1560 × 1019 × 520 mm52 dBR290
HM073HF UB40Three phase7 kW5.007 kW3.467 kW5.243.8675°C1320 × 1019 × 520 mm49 dBR290
HM093HF UB40Three phase9 kW4.709 kW3.159 kW5.203.8675°C1320 × 1019 × 520 mm50 dBR290
HM123HF UB60Three phase12 kW4.7012 kW3.3712 kW5.453.9775°C1560 × 1019 × 520 mm49 dBR290
HM143HF UB60Three phase14 kW4.5014 kW3.2714 kW5.383.9675°C1560 × 1019 × 520 mm51 dBR290
HM163HF UB60Three phase16 kW4.3016 kW3.1716 kW5.113.9275°C1560 × 1019 × 520 mm52 dBR290
Final selection requires design heat loss, design outdoor condition, water temperature, emitter performance, hydraulics, DHW and electrical checks.

How to use this model comparison

Match the full model code and electrical supply first. Capacity and COP at A7/W35 describe a different operating point from A7/W55 or A−7/W35; compare values only at matching conditions. A maximum water temperature is not proof that an existing radiator system meets the building's heat demand.

Prepare an engineering enquiry

Provide design heat loss, required water temperatures, existing emitter details, electrical supply and hot-water demand. Add photographs, proposed unit location and the hydraulic arrangement. Confirm applicable installation documentation and accessories for the exact model. These reference pages do not establish a stocked or commercially supplied product.

Check existing radiators · Prepare the hydraulic arrangement · Read the heat-pump/radiator guide