Product

SOREL MHCC Heating Controller

SOREL MHCC weather-compensated control for a mixed heating circuit. Check sensors, heat request and Datalogger requirements before selection in Cyprus.

SOREL · MHCC

Temperature control class
VI / 4%
of which for PT1000 Temperature sensors
3
of which for Direct Sensors VVX / VFS / RPS Temperature
0
Thermostats

Need price or availability?

Send us the product and the basic project details so we can guide you correctly.

Call us

Weather-compensated control of a mixed heating circuit

SOREL MHCC is a heating-circuit controller for a circuit with a mixing valve and heat request. Its role differs from a solar differential controller such as STDC.

Match the hydraulic and electrical arrangement

Send the heat-source model, mixer and pump details, sensor positions and existing wiring diagram. The manufacturer lists PT1000 inputs and compatibility with °CALEON, RC20 and RC21 room controls. Compatibility with a boiler or heat pump still requires checking the equipment's required signal and the controller's wiring instructions.

The manufacturer lists three 230 V relay outputs and a PWM or 0–10 V output for modulating burner control. It does not list a volt-free relay output. Do not treat a switched-live output as a dry-contact heat request.

Connectivity requires the correct accessories

The manufacturer lists CAN connectivity for SOREL Connect. Ethernet access and microSD logging are listed via a Datalogger, not as built-in MHCC connections. Confirm the required accessory, controller version and connection arrangement before specifying monitoring.

MHCC is not listed for an unmixed heating circuit, cooling or domestic-hot-water control. Where the project needs those functions, review a different controller or complete control design.

Documents and project enquiry

The document list identifies the manual language and distinguishes the second German manual as an alternate document. Match the manual to the controller supplied. Send the existing controller label, circuit diagram and required functions for selection and quotation.

Browse thermostats and heating controls or the heat-pump hydraulic precheck to prepare the system information.

Manufacturer's MHCC specifications

Technical table

SOREL MHCC Heating Controller
SpecificationValue
Temperature control classVI / 4%
Sensor inputs4
of which for PT1000 Temperature sensors3
of which for remote adjuster1
of which for Direct Sensors VVX / VFS / RPS Temperature0
of which for Direct Sensors VVX / VFS / RPS flow0
Compatible room thermostat°CALEON / RC20 / RC21
Relay outputs 230V3
Relay output voltage-free✕
Outputs 0..10V or PWM signal (for modulating burner control)1
24VDC output for external devicesbis zu 2W
Number of applications2
Extension of pre-defined systems by selectable additional functions✕
LEDs red/green for display of operating status✓
Programmable thermostat times and functions per day3
Comfort function for quick heating✓
Heating circuit with mixer✓
Heating circuit without mixer✕
Domestic hot water function with operating times✕
Legionella function via solar✕
Legionella protecion via additional heating✕
Cooling✕
Setup wizard✓
Solar-System protection✕
Solar-Collector protection✕
Buffer discharge protection✓
Anti-freeze protection✓
Seizing Protection✓
Solar-Recooling✕
Start logic for vacuum tube collectors✕
Control program for self-dumping systems (drain-back)✕
Function control and error memory with date and time✓
Error memory and analysis with date and time✓
Input for low energy tariff or PV overproduction (PV contact)✕
Menu blocker✓
CAN bus connection for SOREL Connect✓
Data logging on microSD cardvia Datalogger
Ethernet connectionvia Datalogger
Dimensions Height x Width x Depth in mm163 x 110 x 51
Housing colourRAL 9003
Protection ClassIP40
Mounting Hardware, Spare Fuse and User Manual✓

For an accurate quote, send us

  • Where the product will be used
  • Quantity or dimensions where available
  • Photos, drawings or material list if available
  • Whether you need store collection or delivery
CallQuote